eHouse.PRO Intelligent Building configuration of intelligent digital inputs
eHouse.PRO Smart Home – functionality and configuration of intelligent digital inputs.
Digital inputs, available on the I/O module with full support of eHouse.PRO server application (for Linux) have a very high functionality. Complete configuration of the digital inputs is independent for each security zone / inputs programs and is loaded with its changing.
The configuration is independent for each digital input (on/off ), alarm output, etc..
Digital inputs beside input noise RC filter are protected with software algorithms, against too rapid changes e.g. due to interference near the wire, lightning in the area. Too short pulses on the inputs are ignored for system security and protection of devices connected to the outputs, eliminating the effect of “Christmas tree” , found in some low-voltage systems.
Due to the digital signal processing on the input and analysis software functionality is much greater than conventional switches or alarm inputs . In addition, the functionality of these inputs can be expanded with new algorithms and ideas , through eHouse.PRO server software upgrade.
All inputs are treated individually and are equally privileged.
Any intelligent input has a number of advanced features:
- The possibility of reversal of input (Invert) – {Inv}
- Security mask for alarm outputs and functions
- * Software Alarm {A}
- * Horn – siren {H}
- * Warning {W}
- * Early Warning {E}
- * Monitoring {M}
- * Quiet/Silent alarm {Q}
- * SMS – notification {S}
- Event triggered when the input is activated – Event Code and described individually in the { Event Name}
- block the events associated with the input {D}
- Programmable time to remember the state of the input
- Delay Timers for each output and function to about 18h with 1s resolution:
- * Alarm
- * Horn
- * Warning
- * Monitoring
- * SMS
- * Early Warning
- * Silent / Quiet
- Timers engagement length and function of each output to around 18h with 1s resolution:
- * Alarm
- * Horn
- * Warning
- * Monitoring
- * SMS
- * Early Warning
- * Silent / Quiet
Alarm output states and functions associated with intelligent inputs, supported by the server are sums of the above parameters for each input.
Delay Timers are of particular importance in the case, the activation of the alarm sensor switches on the actuator, “testing” counteract the cause of the activation of the sensor.
For example:
We have a pumping sewage or drainage wells requiring mechanical pumping liquids:
- Intelligent input connected the liquid level sensor
- Set an event associated with the activation of the input actuating the pump in the well connected to any output (ON/OFF) ( for a short time : a few minutes to pump had a chance to empty wells )
- Set the delay time for alarm signals (alarm , horn , warning , etc. ) slightly larger than the pump on time
- Set the required mask activating alarm signals from a particular input
In the above example, the activation of the sensor will turn on the pump for a preset time.
1 ) If the pump for any reason ( lack of electricity , damage to the pump , etc.. ) not empty wells in the preset delay time of alarm signals, alarm will be activated in accordance with security mask set.
2 ) If the pump empties the well at the right time, alarm is not activated at all.
Configuration of inputs as well as the entire eHouse.PRO smart building system is accomplished through the web browser on a form which contains all the settings for inputs, using the syntax appropriate address or stranded: v.x.s.z/ehouse.pro/inputs.php?func=advancedsettings&filter=inputs&program=3 field “program” contains no protection zone (zone/program), for which we create a configuration.
A copy of the configuration screen : eHouse.PRO Smart House configuration of inputs. When starting for the first time configuration for the program/zone should set the default parameters (time delay integration, and the length of the inclusion of alarm outputs ) in the fields { Defaults } . In this case, check the box {Update} Defaults and press {Update}
For a = 0 we create a default configuration and length of the delay times , which will be copied to other programs , the creation of the default settings .
Note !!!
Description of fields:
defaults – default values when copying configurations
Delays – activation delay of alarm outputs and functions
Length – the duration of the signal on alarm outputs and functions
Time is saved in the format h: m:s ( hours:minutes:seconds)
{ Alarm [A] } – time for a software alarm in square brackets brief description of the mask Security ” A ” – alarm
{ Horn [H] } – output siren
{ Warning [W] } – light output warning
{ Early Warning [E] } – exit early warning
{Monitoring [M] } – output in radio monitoring
{ SMS [S] } – send SMS alarm notifications from the GSM module
{ Quiet [Q] } – Output silent alarm
{ State [I] } – time to remember the status of the input activation
In addition, the option { Inv } denoting the reversal of the importance of input ( negation )
{D} is blocking the implementation of an event associated with the entry
Then, the table contains the configuration of all input fields with descriptions :
{ No. } – Number Inputs
{ Name} – Name input ( if it begins ” @ ” does not appear in the list of status )
{ Inv } – Reversal of the importance of input ( negation )
{ Delays } – Delay for outputs and alarm signals
{ Length } – the length of time the inclusion of outputs and alarm signals
{A H W E M S Q D} – Masks security ( alarm output ) and functions (SMS , Lock start of the event)
{Event Name} – Event name associated with the entry ( individual description)
{Event Code} – copied event code to run when you activate the input
After setting the required configuration , assigning events to enter , press { Update }
More about eHouse.PRO : Intelligent Building eHouse.PRO
Shopping on the Internet :
building automation eHouse.PRO Server
smart home eHouse . PRO entry